Explore GE Vernova
Resource Library
Get access to curated content, tools, and useful resources to help you face all your grid challenges.
Access the library
Electrification Businesses
Electrification Software
Power Conversion
Solar & Storage Solutions
Category banner
Banner image
Protection Relays
Feeder Protection

Home > Grid Automation > Protection Relays > Feeder Protection > Multilin Agile Feeder Protection

Product Lookup
Protection & Control Online Store (new window)
Protection & Control Support
Event Calendar
Protection & Control Press Room
Related Links
  Interactive Selector Guide
  Spotlight Application
  Typical Applications
  Feeder Principles & Protection
  GSA Schedule
  Industrial Energy Management Systems
  Legacy Feeder Protection

  

Multilin Agile

Compact Feeder Protection and Bay Controller

GE’s Multilin Agile Feeder Protection solution offers advanced protection, monitoring, and control for utilities, industrial plants, onshore and offshore renewable collectors, and more. Serving as primary or backup feeder protection, it is equipped with advanced communication options and extensive monitoring capabilities.

Applicable to distribution and industrial feeders, this powerful yet compact device features a graphical color display for presenting configurable Single Line Diagrams that enables bay monitoring and control. It also provides distribution feeder protection for the detection of faults on compensated networks, and load encroachment on heavily loaded lines.

Key benefits:

  • Small footprint for easy retrofitting of aging infrastructure
  • Intuitive graphical display for effective monitoring, communications, and troubleshooting
  • Advanced functions addressing the challenges of renewable integration
  • CyberSentry™ Advanced Cybersecurity to prevent unauthorized access and cyber attacks
  • Draw-out design for simplified testing, commissioning, and maintenance
  • Cost savings on engineering time and wiring
What is Multilin Agile
Overview
User Interface
Product Explorer

What is Multilin Agile?

Multilin Agile is a compact feeder protection and bay controller device with extensive protection, control, and communications capabilities. The design ensures that performance, sensitivity, customization, and flexibility are delivered along with minimized configuration and commissioning effort. The device is configured using software with few order code variants, providing standardization that mitigates the risk of mis-ordering, enables easy stocking, and reduces spare inventory.

Intuitive software and graphical display streamline and declutter the settings menu by hiding unnecessary elements. Default applications are pre-loaded and a simple configuration column readies the product for application from a single touchpoint for effective monitoring, communications, and troubleshooting.

Multilin Agile 6 inch case

The draw-out design permits fast extraction and insertion with inherent safety features to minimize risks associated with open-circuit CTs. The relay’s printed circuit boards have harsh environmental coating as the standard, to shield from contaminants such as moisture, salt mist, and atmospheric pollution, extending operational life.

Multilin Agile housed in a 30TE (6 inch) wide case supports integrated color graphical display. The device provides advanced functionality, including high-performance protection, extensive monitoring and control functions, redundant Ethernet communication, higher I/O density of up to 30 inputs / 25 outputs, and flexible configuration capabilities in a compact form factor and shallow depth of less than 155 mm behind panels.

In case a standard LCD text display is needed, please refer to P40 Agile Enhanced offering

Overview

Multilin Agile Feeder P14D Functional Block Diagram
P40AE Functional Block Digram
ANSI® Device Numbers and Functions
Device Number Function
21BL Load encroachment supervision (Load blinders)
24 Volts per Hertz
25 Check Synchronising
27 Phase and Line Undervoltage
27V Positive Suquence Undervoltage
27Q UV Reactive Power
27T Timed Undervoltage
32 Phase Directional Power
32N Wattmetric Ground Fault
37 Undercurrent
46 Negative Sequence Overcurrent
47 Negative Sequence Overvoltage
49 Thermal Overload
50/27 Switch-on to Fault
50 Phase Definitive Time Overcurrent
51 Phase Inverse-Time Overcurrent
Device Number Function
52 Breaker and Isolator Control
52PD Pole Discrepancy
55 Power Factor
59 Phase and Line Overvoltage
59V Positive Sequence Overvoltage
67 Directional Phase Overcurrent
68 Inrush Blocking
79 Autoreclose
86 Latching/Lockout Contacts
21FL Fault Locator
46BC Broken Conductor
50BF CB Failure
50N/G Neutral/Ground Definitive Time Overcurrent
51N/G Neutral/Ground IDMT Overcurrent
SEF Sensitive Earth Fault
51R Voltage Restrained Overcurrent
Device Number Function
51V Voltage Controlled Overcurrent
67_2 Directional Negative Sequence Overcurrent
59N Neutral Voltage Displacement
67N Directional Neutral/Ground Overcurrent
81df/dt Rate of Change Frequency
81O Overfrequency
81U Underfrequency
81V Undervoltage Blocking
87G Restricted Ground Fault (REF)
CLP Cold Load Pick Up
CTS/VTS CT and VT Supervision
  DC Supply Monitoring
  Fast underfrequency
  Underfrequency Restoration
TGFD Transient Ground Fault Detection
THD Hamonic Measurement/Protection
YN Neutral Admittance

Advanced Communications

Three communication ports are standard: a rear serial port providing remote communications, a front USB port, and a rear Ethernet for device configuration and management.

Two additional Ethernet ports can be ordered to achieve Ethernet communication redundancy.

Supported Communication Protocols Include:

  • Modbus (RS485 serial or Ethernet)
  • IEC 60870-5-103
  • DNP 3.0 (RS485 serial or Ethernet)
  • IEC 61850 Ed. 2 with concurrent serial connection
  • Redundant Ethernet protocols PRP, HSR, and failover also available with dual RJ45 or dual fiber media

Flexible Hardware

  • Space-saving 4U height with 6" (30TE) case size
  • Wide choice of opto-isolated binary inputs and output relays
  • Binary inputs ESI 48-4 EB2 compliant – avoids spurious pickup from induction on field wiring
  • High density I/Os in various combinations depending on case size option
  • Ungrouped binary inputs for trip circuit supervision
  • Field upgradeable, avoiding costly hardware changes
  • 6" (30TE) models can accommodate:
    • 1 x RS485/IRIG-B interface
    • Up to 3 x RJ45/fiber optic ports for single and redundant Ethernet plus additional engineering access
    • From 11 to 30 binary inputs, and 9 to 25 relay outputs, depending on the order code

Simulation & Testing

To aid commissioning, a simulation feature is provided to test the relay’s functionality and response to programmed conditions, without the need for external AC voltage and current inputs. When placed in simulation mode, the relay suspends reading actual AC inputs, generates samples to represent the programmed phasors, and loads these samples into the memory to be processed by the relay. Normal (pre-fault), fault, and post-fault conditions can be simulated to exercise a variety of relay features. Other test operations, such as an LED lamp testing for each color, contact input states, and testing of output relays, are also possible.

Application Model Selection

Model Hardware Base Intended Application Case Model
P14NB P14N Non-directional feeder 30TE
P14NL P14N

Non-directional feeder with autoreclose

30TE

P14DB

P14D

Directional feeder

30TE

P14DL

P14D

Advanced directional feeder with autoreclose and check synchronising

30TE

P14DZ

P14D

Advanced directional feeder with TGFD transient ground fault detection

30TE
P94VB P94V

Voltage and frequency

30TE
P94VP P94V

Voltage and frequency with autoreclose and check synchronising

30TE

Intuitive User interface

Multilin Agile 30TE User Interface

Multilin Agile front panel interface – ANSI version

The front HMI hosts a fully graphical color screen. The front panel supports open, close, local/remote, and direct function key access, facilitating the control of connected switchgear and managing up to six controllable devices. These replace traditional hardwired control scheme switches and annunciation, saving on engineering time and wiring costs.

Sixteen tricolor LED lamps are available and freely configurable, in addition to four fixed-function LEDs that provide a cost-effective solution for annunciation.

Multiple languages are supported with easy switching between English and an additional language on the local display without uploading new firmware.

A USB front port allows ready access by field personnel laptops.

Intuitive Graphical Display

P40AE Phasor View P40AE Extensive Recording P40AE AC Analog Measurements P40AE Enhanced Bay visualization and Control
Phasor view for effective monitoring, commissioning & troubleshooting   Extensive recording for in-depth post-fault analysis   Accurate, real-time display of AC analog measurements   Enhanced bay visualization & control aided by single line diagram display

Product Explorer

Multilin Agile Product Explorer